Georgetown home inspections

Sample Report

Home 1 Year Builder's Warranty Inspections ~ Pre-Inspections ~ Contact Us

Below is a sample of the typical report from Safe and Sound Inspections

 

Prepared for:    Mrs. Jane Client

Concerning:   address confidential, Texas

By:   Eric Laney, Lic. No. 8566       December 20, 2005

The inspection of the property listed above must be performed in compliance with the rules of the Texas Real Estate Commission (TREC). The inspection is of conditions which are present and visible at the time of the inspection, and all of the equipment is operated in normal modes. The inspector must indicate which items are in need of repair or are not functioning and will report on all applicable items required by TREC rules. This report is intended to provide you with information concerning the condition of the property at the time of inspection. Please read the report carefully. If any item is unclear, you should request the inspector to provide clarification. It is recommended that you obtain as much history as is available concerning this property. This historical information may include copies of any seller's disclosures, previous inspection or engineering reports, reports performed for or by relocation companies, municipal inspection departments, lenders, insurers, and appraisers. You should attempt to determine whether repairs, renovation, remodeling, additions or other such activities have taken place at this property. Property conditions change with time  and use. Since this report is provided for the specific benefit of the client(s), secondary readers of this information should hire a licensed inspector to perform an inspection to meet their specific needs and to obtain current information concerning this property.


ADDITIONAL INFORMATION PROVIDED BY INSPECTOR

Outdoor temperature was 71degrees at time of inspection. No rain at time of inspection.

Additional pages may be attached to this report. Read them very carefully. This report may not be complete without the attachments. If an item is present in the property but is not inspected, the "NI" column will be checked and an explanation is necessary. Comments may be provided by the inspector whether or not an item is deemed in need of repair.

I=Inspected NI=Not Inspected NP=Not Present R=Not Functioning or In Need of Repair

I

NI

NP

R

Inspection Item

I. Structural Systems

X

X

A. Foundations (If all crawl space areas are not inspected, provide an explanation.)
Comments (An opinion on performance is mandatory.):
No cracks noted, performing as designed at time of inspection.

X

X

B. Grading and Drainage
Comments:
Grading appeared to be adequate. Home does not have gutters installed. Due to clay soil, it is advisable for all homes in Central Texas to have gutters installed that divert rainwater at least 5 feet from the foundation.

X

X

C. Roof Covering
1) Two shingles are torn on roof of front porch.

2) Several roof vents had unsealed nails
3) One roof vent has sharp raised edges under the shingles. The metal flashing is lifting the shingles at each side of the box and will eventually tear the shingles. Raised edges should be flattened and shingles sealed onto flashing.
4) Garage roof to wall flashing at gables has several unsealed fasteners (front and back of garage)

X

X

D. Roof Structure and Attic

Comments: Due to low roof height, the attic was inspected from the attic access door while on a ladder. Blown insulation depth was 15"
1) Garage roof decking has four holes, one at each corner near hip rafter. This will eventually cause the shingles to fail, either by foot traffic during maintenance or through weather damage. It is also unsafe for foot traffic and may lead to a falling injury.

X

X

E. Walls (Interior and Exterior)
Comments:
1) Siding has a gap at upper right corner of 2nd story front window. Gap leads to sheathing and will allow water penetration into wall. This gap must be sealed.

2) All exterior trim is not sealed around doors, windows, and corners. This allows water penetration and should be sealed.

3) Several butt joints in the siding were not caulked. Caulk all joints to prevent water intrusion.

4) Anchor bolts in garage are breaking through edge of bottom plate. Shot driven nails are not an approved substitute for anchor bolts in exterior walls. Replace with bolts and maintain proper distance from edge of bottom plate.

X

X

F. Ceilings and Floors
Comments:
1) Client states that several nails had popped in the ceiling drywall, and cracks had formed near the ceiling/wall intersection. At time of inspection they were repaired by builder. This is sometimes caused by shrinkage of the lumber in new construction. This can also be caused by truss uplift on the upstairs ceilings, a seasonal rise and fall of the roof trusses with no known repair. The nails may continue to pop in the future and will require routine patch/paint repair. There was no visible evidence of foundation or structural movement that would cause this.

2) Minor movement noted in second story plywood subfloor when walking on floor. Client stated that the builder already agreed to repair.

X

G. Doors (Interior and Exterior)
Comments:
No problems noted at time of inspection

X

H. Windows
Comments:
No fogging noted in double glazed windows at time of inspection

X

I. Fireplace/Chimney
Comments:
Not Installed

X

J. Porches, Decks and Carports (Attached)
Comments:
No problems noted at time of inspection

X

K. Other

Comments:

 

I

NI

NP

R

Inspection Item

II. ELECTRICAL SYSTEMS

X

X

A. Service Entrance and Panels
Comments:
Shrubbery is planted directly in front of service panel. For safety of maintenance personnel the shrubbery should be removed.

X

B. Branch Circuits - Connected Devices and Fixtures
(Report as in need of repair the lack of ground fault circuit protection where required.): Comments:

III. HEATING, VENTILATION AND AIR CONDITIONING SYSTEMS

X

A. Heating Equipment

Type and Energy Source: Gas forced air furnace

Comments: No problems noted at time of inspection

X

X

B. Cooling Equipment:

Type and Energy Source: Electric split system central air

Comments: Filters were dirty. Supply and return air temp difference adequate.

X

C. Ducts and Vents

Comments: No problems noted at time of inspection

IV. PLUMBING SYSTEM

X

A. Water Supply System and Fixtures
Comments:
No problems noted at time of inspection

X

B. Drains, Wastes, Vents
Comments:
No problems noted at time of inspection

X

C. Water Heating Equipment (Report as in need of repair those conditions

specifically listed as recognized hazards by TREC rules.)

Comments: Energy source Gas  No problems noted at time of inspection

 

X

D. Hydro-Therapy Equipment
Comments:

V. APPLIANCES

X

X

A. Dishwasher
Comments:
Dishwasher does not work. Fills only, does not run through cycles.

I=Inspected NI=Not Inspected NP=Not Present R=Not Functioning or In Need of Repair

I

NI

NP

R

Inspection Item

X

B. Food Waste Disposer
Comments:
No problems noted at time of inspection

X

C. Range Hood
Comments:
No problems noted at time of inspection

X

D. Ranges/Ovens/Cooktops
Comments:
Oven temp was 340 when set to 350, within limits of +/-25 degrees.

X

E. Microwave Cooking Equipment
Comments:
No problems noted at time of inspection

X

F. Trash Compactor
Comments:
Not Installed

X

G. Bathroom Exhaust Fans and/or Heaters
Comments:
No problems noted at time of inspection

X

H. Whole House Vacuum Systems
Comments:

X

X

I. Garage Door Operators
Comments:
1) Electric eye sensor does not work, appears to be misaligned. This is a safety hazard and should be repaired.
2) Electric eye height should be 5 to 6" , actual height is 8.5". This is a safety hazard and should be adjusted.

X

J. Door Bell and Chimes
Comments:
No problems noted at time of inspection

X

K. Dryer Vents
Comments:
No problems noted at time of inspection

X

L. Other Built-in Appliances
Comments:

I=Inspected NI=Not Inspected NP=Not Present R=Not Functioning or In Need of Repair

I

NI

NP

R

Inspection Item

VI. OPTIONAL SYSTEMS

X

A. Lawn Sprinklers
Comments : Not included in standard inspection per Texas Real Estate Commission

X

B. Swimming Pools and Equipment
Comments: Not included in standard inspection per Texas Real Estate Commission

X

C. Outbuildings
Comments: Not included in standard inspection per Texas Real Estate Commission

X

D. Outdoor Cooking Equipment
Comments: Not included in standard inspection per Texas Real Estate Commission

X

 

E. Gas Lines
Comments: Not included in standard inspection per Texas Real Estate Commission

X

F. Water Wells (A coliform analysis is recommended.)

Comments: Not included in standard inspection per Texas Real Estate Commission

X

G. Septic Systems
Comments: Not included in standard inspection per Texas Real Estate Commission

X

H. Security Systems
Comments: Not included in standard inspection per Texas Real Estate Commission

X

I. Fire Protection Equipment
Comments: Not included in standard inspection per Texas Real Estate Commission

 

Summary Page

The summary page is provided for reference purposes only and may not reflect all of the inspection findings. It is not intended for use as the official inspection report on the subject property. Please refer to the full report for the entire list of inspection findings.

 

Foundations No cracks noted, performing as designed at time of inspection.

Grading and Drainage Grading appeared to be adequate. Home does not have gutters installed. Due to clay soil, it is advisable for all homes in Central Texas to have gutters installed that divert rainwater at least 5 feet from the foundation.

Roof Covering 1) Two shingles are torn on roof of front porch. 2) Several roof vents had unsealed nails 3) One roof vent has sharp raised edges under the shingles. The metal flashing is lifting the shingles at each side of the box and will eventually tear the shingles. Raised edges should be flattened and shingles sealed onto flashing. 4) Garage roof to wall flashing at gables has several unsealed fasteners (front and back of garage)

Roof Structure and Attic Comments: Due to low roof height, the attic was inspected from the attic access door while on a ladder. Blown insulation depth was 15" 1) Garage roof decking has four holes, one at each corner near hip rafter. This will eventually cause the shingles to fail, either by foot traffic during maintenance or through weather damage. It is also unsafe for foot traffic and may lead to a falling injury.

Walls (Interior and Exterior) Comments: 1) Siding has a gap at upper right corner of 2nd story front window. Gap leads to sheathing and will allow water penetration into wall. This gap must be sealed. 2) All exterior trim is not sealed around doors, windows, and corners. This allows water penetration and should be sealed.3) Several butt joints in the siding were not caulked. Caulk all joints to prevent water intrusion. 4) Anchor bolts in garage are breaking through edge of bottom plate. Shot driven nails are not an approved substitute for anchor bolts in exterior walls. Replace with bolts and maintain proper distance from edge of bottom plate.

Ceilings and Floors Comments: 1) Client states that several nails had popped in the ceiling drywall, and cracks had formed near the ceiling/wall intersection. At time of inspection they were repaired by builder. This is sometimes caused by shrinkage of the lumber in new construction. This can also be caused by truss uplift on the upstairs ceilings, a seasonal rise and fall of the roof trusses with no known repair. The nails may continue to pop in the future and will require routine patch/paint repair. There was no visible evidence of foundation or structural movement that would cause this. 2) Minor movement noted in second story plywood subfloor when walking on floor. Client stated that the builder already agreed to repair.

Service Entrance and Panels Comments: Shrubbery is planted directly in front of service panel. For safety of maintenance personnel the shrubbery should be removed.

Cooling Equipment: Filters were dirty. Supply and return air temp difference adequate.

Garage Door Operators Comments: 1) Electric eye sensor does not work, appears to be misaligned. This is a safety hazard and should be repaired. 2) Electric eye height should be 5 to 6" , actual height is 8.5". This is a safety hazard and should be adjusted.